
EDUS39-900A-F11_a Electric Characteristics
FXMQ-M 7
6. Electric Characteristics
NOTES:
1. Voltage range: Units are suitable for use on
electrical systems where voltage supplied to unit
terminals is not below or above listed range limits.
2. Maximum allowable voltage imbalance between
phases is 2%.
3. MCA/MOP
MCA = 1.25 X FLA
MOP <
4 x FLA
(next lower standard fuse rating: Min. 15A)
4. Select wire based on the MCA.
5. Instead of a fuse, use a circuit breaker.
SYMBOLS:
MCA: Minimum Circuit Amps (A)
MOP: Maximum Overcurrent Protection (A)
kW: Fan Motor Rate Output (kW)
FLA: Full Load Amps (A)
IFM: Indoor Fan Motor
Units Power supply IFM Input (W)
Model Hz Volts Voltage range MCA MOP kW FLA Cooling Heating
FXMQ72MVJU
60 208-230
MAX. 253
MIN. 187
9.5 15 0.380 x 2 7.6 1,490 1,490
FXMQ96MVJU 10.7 15 0.380 x 2 8.6 1,684 1,684
Kommentare zu diesen Handbüchern