Installation EDUS39-900A-F11_a
24 FXMQ-M
10. FIELD SETTING
Make sure the terminal box lids are closed on the indoor
and outdoor units.
Field setting must be made from the remote controller in
accordance with the installation condition.
Setting can be made by changing the “Mode No.”, “FIRST
CODE NO.”, and “SECOND CODE NO.”.
For setting and operation, refer to the “FIELD SETTING” in
the installation manual of the remote controller.
Set the remote controller to the field set mode. For
details, refer to the “HOW TO SET IN THE FIELD”, in
the remote controller manual.
When in the field set mode, select mode No. 12, then
set the first code (switch) No. to “1”. Then set second
code (position) No. to “01” for FORCED OFF and “02”
for ON/OFF OPERATION. (FORCED OFF at factory
set)
11. TEST OPERATION
Refer to the installation manual of the outdoor unit.
The operation lamp of the remote controller will flash when
an malfunction occurs. Check the malfunction code on the
liquid crystal display to identify the point of trouble. An
explanation of malfunction codes and the corresponding
trouble is provided in “CAUTION FOR SERVICING” of the
outdoor unit.
If any of the items in Table 3 are displayed, there may be a
problem with the wiring or power, so check the wiring again.
Ta b l e 3
3P086156-13Y
Remote control display Content
“Concentrated Management”
is lit up
There is a short circuit at the
FORCED OFF terminals (T1,
T2)
“U4” is lit up
“UH” is lit up
The power on the outdoor unit is
off.
The outdoor unit has not been
wired for power supply.
Incorrect wiring for the transmis-
sion wiring and / or FORCED
OFF wiring.
No display
The power on the indoor unit is
off.
The indoor unit has not been
wired for power supply.
Incorrect wiring for the remote
controller wiring, the transmis-
sion wiring and / or the
FORCED OFF wiring.
SETTING
MODE NO.
SECOND
CODE NO.
FIELD SET
MODE
FIRST
CODE NO.