EDUS39-900A-F11_a Specifications
FXMQ-M 3
2. Specifications
Ceiling Mounted Duct Unit
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure means “High static pressure-
Standard”.
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
Model FXMQ72MVJU FXMQ96MVJU
1 Cooling Capacity Btu/h 72,000 96,000
2 Heating Capacity Btu/h 81,000 108,000
Casing / Color Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) in. 18’-1/8’’×54’-3/8’’×43’-5/16’’ 18’-1/8’’×54’-3/8’’×43’-5/16’’
Coil (Cross
Fin Coil)
Rows×Stages×FPI 3×26×13 3×26×13
Face Area ft² 7.32 7.32
Fan
Model D13/4G2DA1×2 D13/4G2DA1×2
Type Sirocco Fan Sirocco Fan
Motor Output (High) W 380×2 380×2
Air Flow Rate (H/L) cfm 2,047/1,764 (H/L) 2,541/2,188 (H/L)
Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Air Filter 5—5
Piping
Connections
Liquid Pipes in. φ3/8 (Flare Connection) φ3/8 (Flare Connection)
Gas Pipes in. φ3/4 (Flare Connection) φ7/8 (Flare Connection)
Drain Pipe in. PS1B PS1B
Machine Weight (Mass) Lbs 302 302
Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve
Connectable outdoor unit R-410A P Series R-410A P Series
Standard Accessories
Operation manual, Installation manual, Sealing pads,
Connection pipes, Screws, Clamps
Operation manual, Installation manual, Sealing pads,
Connection pipes, Screws, Clamps
Drawing No. C:3D065683