Installation EDUS39-900A-F11_a
20 FXMQ-M
7. DRAIN PIPING WORK
Rig the drain pipe as shown below and take measures
against condensation. Improperly rigged piping could
lead to leaks and eventually wet furniture and belong-
ings.
Insulate the drain hose inside the building.
(1) Carry out the drain piping.
Keep piping as short as possible and slope it down-
wards so that air may not remaine trapped inside the
pipe.
Keep pipe size equal to or greater than that of the con-
necting pipe (Vinyl pipe of 1in. nominal diam. and
1-1/4in. outer diam.).
Insulate the clamp metal with the sealing pad.
In order to prevent foreign matter from building up
inside the piping, you should avoid curves as much
as possible.
NOTE
If converging multiple drain pipes, install according to the
procedure shown below.
A drain trap need not be installed.
The diameter of the piping is the same as that of the
connecting pipe (PS1B), and should be kept equal to or
greater than that of the connecting pipe.
(2) After piping work is finished, check drainage flows
smoothly.
Open the water supply port, add appximately 61in
3
. of
water slowly into the drain pan and check drainage flow.
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes
that smell of ammonia. The ammonia in the sewage might
enter the indoor unit through the drain pipes and corrode
the heat exchanger.
8. ELECTRIC WIRING WORK
8-1 GENERAL INSTRUCTIONS
All field supplied parts and materials and electric works
must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also “Wiring diagram label”
attached to the electrical components box lid.
For remote controller wiring details, refer to the installation
manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit and BS unit are properly
matched. If wiring and piping between the outdoor unit and
an indoor unit are mismatched, the system may cause a
malfunction.
A ground fault circuit interrupter capable of shutting down
power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit
for the size of power supply wiring connected to the outdoor
unit, the capacity of the ground fault circuit interrupter and
switch, and wiring instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas and water pipes,
lightning rods, or telephone ground wires.
Gas pipes : might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is
used.
Telephone ground wires or lightning rods : might cause
abnormally high electric potential in the ground during
lighting storms.
8-2 ELECTRICAL CHARACTERISTICS
MCA: Minimum Circuit Amps (A); MOP: Maximum
Overcurrent Protection; kW: Fan Motor Rated Output (kW);
FLA: Full Load Amps (A)
Bottom of unit
Attached drain hose
Metal clamp
Drain hoseTape
1/8in. or less
Drain hose
Sealing pad
(Field supply)
Metal clamp
(Field supply)
3-15/16in.
or more
Units Power supply Fan motor
Model Hz Volts
Voltage
range
MCA MOP W FLA
FXMQ72MVJU
60
208-
230
Max. 253
Min. 187
9.5 15
380×2
7.6
FXMQ96MVJU
10.7 15
380×2
8.6