EDUS39-900A-F11_a Installation
FXMQ-M 23
9-3
CONTROL BY 2 REMOTE CONTROLLERS
(Controlling 1 indoor unit by 2 remote control-
lers)
When using 2 remote controllers, one must be set to
“MAIN” and the other to “SUB”.
MAIN/SUB CHANGEOVER
(1) Insert a screw driver into the recess between the upper
and lower part of remote controller and, working from the
2 positions, pry off the upper part.
The remote controller PC board is attached to the upper
part of remote controller.
(2) Turn the MAIN/SUB changeover switch on one of the two
remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to
“M”.)
Wiring Method (See ‘‘ELECTRIC WIRING WORK’)
(3) Remove the electrical components box lid
(4) Add remote control 2 (slave) to the terminal block for
remote controller (P
1
, P
2
) in the electrical compo-
nents box.
(There is no polarity.) (Refer to Fig. 3 and 8-3.)
9-4 COMPUTERISED CONTROL (FORCED OFF
AND ON/OFF OPERATION)
(1) Wire specifications and how to perform wiring
Connect the input from outside to terminals T1 and T2
of the terminal block for remote controller.
(2) Actuation
The following table explains FORCED OFF and ON/
OFF OPERATIONS in response to Input A.
(3) How to select FORCED OFF and ON/OFF OPERATION
Turn the power on and then use the remote controller to
select operation.
9-5 CENTRALIZED CONTROL
For centralized control, it is necessary to designate the
group No. For details, refer to the manual of each optional
controllers for centralized control.
Upper part of
remote controller
Lower part of
remote controller
Insert the screwdriver here and gently work
off the upper part of remote controller.
Only one remote
controller needs to be
changed if factory
settings have
remained untouched.
(Factory setting)
S
M
S
S
M
Remote controller
PC board
Wire specification Sheathed vinyl cord or cable (2 wire)
Gauge AWG18-16
Length Max. 328ft.
External terminal
Contact that can ensure the minimum appli-
cable load of 15 V DC, 1 mA.
FORCED OFF ON/OFF OPERATION
Input “ON” stops operation (impossible by
remote controllers.)
Input OFF ON
turns ON unit.
Input OFF enables control by remote con-
troller.
Input ON OFF
turns OFF unit.
F2 T1 T2
FORCED
OFF
Input A