Troubleshooting by Remote Control ESIE09-08A
132 Troubleshooting
2.2 Self-diagnosis by Wired Remote Control
Explanation If operation stops due to malfunction, the remote control’s operation LED blinks, and malfunction code is
displayed. (Even if stop operation is carried out, malfunction contents are displayed when the inspection
mode is entered.) The malfunction code enables you to tell what kind of malfunction caused operation to
stop. See
page 137 for malfunction code and malfunction contents.
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or more
will clear the failure history indication shown above. In this case, on the codes display, the malfunction
code will blink twice and then change to “00” (=Normal), the Unit No. will change to “0”, and the
operation mode will automatically switch from check mode to normal mode (displaying the set
temperature).
3. Subcode is needed to indicate which refrigerant system is causing the error.
Inspection display
Inspection/Test button
ON/OFF button
Operation LED
Malfunction code
with subcode