ESIE09-08A Basic Control
Function 55
2. Basic Control
2.1 Normal Operation
Heating Operation Outdoor Unit
Heating operation is not functional at an outdoor air temperature of field setting [9-02]. Default [20°C - 24°C].
Heating Operation Indoor Unit
Actuator Operation Remarks
Compressor Compressor PI control
Used for high pressure protection control, low pressure
protection control, discharge pipe temperature
protection control, and compressor operating frequency
upper limit control with inverter protection control.
Outdoor unit fan STEP 7 or 8 All steps possible, mainly STEP 7 OR 8
Four way valve ON
Main electronic expansion valve (EV1) PI control
Subcooling electronic expansion valve
(EV3)
PI control
Hot gas bypass valve (SVP) OFF This valve turns on with low pressure protection control.
Actuator Operation Remarks
Compressor Compressor PI control
Used for high pressure protection control, low pressure
protection control, discharge pipe temperature
protection control, and compressor operating frequency
upper limit control with inverter protection control.
Four way valve (Y1R) OFF Only activated during defrost.
Two way valve (K2S) = solenoid valve CLOSED Only open during defrost.
Electronic expansion valve (K1E) PI control
Electronic expansion valve (K2E) PI control
DC inverter pump PI control