ESIE09-08A Troubleshooting by Indication on the Remote Controller
Troubleshooting 147
3.5 “AJ ” Indoor Unit: Malfunction of Capacity Determination
Device
Remote Control
Display
AJ
Subcode 0
Applicable Models All indoor unit models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adapter and the memory inside the
IC memory on the indoor unit PC board, and whether the value is normal or abnormal is determined.
Malfunction
Decision Conditions
Operation and:
1. When the capacity code is not contained in the PC board’s memory, and the capacity setting adapter is
not connected.
2. When a capacity that doesn’t exist for that unit is set.
Supposed Causes You have forgotten to install the capacity setting adapter.
Defect of indoor unit PC board (A4P).
Troubleshooting
(V2783)
Caution
Install a capacity setting adapter.
Replace the indoor unit PC board.
(A4P)
NO
NO
YES
YES
Replace the indoor unit PC
board. (A4P)
The indoor
unit PC board was
replaced with a replacement
PC board.
The
indoor unit is a
model that requires
installation of a capacity
setting adapter when
replacing the PC
board.