Troubleshooting by Indication on the Remote Controller ESIE09-08A
142 Troubleshooting
3. Troubleshooting by Indication on the Remote
Controller
3.1 “A1 Indoor Unit: PC Board Defect
Remote Control
Display
A1
Subcode 0
Applicable Models All indoor unit models
Method of
Malfunction
Detection
Check data from E²PROM.
Malfunction
Decision Conditions
When data could not be correctly received from the E²PROM
E²PROM: Type of nonvolatile memory. Maintains memory contents even when the power supply is
turned off.
Supposed Causes Defect of indoor unit PC board
Troubleshooting
Turn power supply OFF, then
power ON again.
Does the system
return to normal?
YES
Caution
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PC
board (A1P).
(V2777)
NO
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.