Installation manual
6
EKHVH/X016BB6V3 + EKHVH/X016BB6+9WN
Daikin Altherma indoor unit
4PW64331-1 – 07.2010
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
Space heating and cooling
According to the season, the customer will select heating or cooling
through the user interface on the indoor unit.
The outdoor unit (1) will operate in heating mode or cooling mode to
achieve the target leaving water temperature.
With the unit in heating mode, the 2-way valve (13) is open. Hot water
is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the 2-way valve (13) is closed to
prevent cold water running through the floor heating loops (FHL).
The ON/OFF setting of the heating/cooling operation is done by the
user interface on the indoor unit.
Application 5
Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin indoor unit or by an
auxiliary boiler connected in the system. The decision whether either
the EKHV* indoor unit or the boiler will operate can be achieved by an
auxiliary contact or an EKHV* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat,
an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 6.
The EKHV* indoor unit controlled contact (also called 'permission
signal for the auxiliary boiler") is determined by the outdoor
temperature (thermistor located at the outdoor unit). See "Field wiring
configuration B" on page 6.
Bivalent operation is only possible for space heating operation, not
for the domestic water heating operation. Domestic hot water in such
an application is always provided by the domestic hot water tank
which is connected to the Daikin indoor unit.
The auxiliary boiler must be integrated in the piping work and in the
field wiring according to the illustrations below.
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Shut-off valve
8 Collector (field supply)
9 Motorised 3-way valve (delivered with the domestic hot
water tank)
11 Domestic hot water tank (optional)
12 Heat exchanger coil
15 Boiler (field supply)
16 Aquastat valve (field supply)
17 Shut-off valve (field supply)
18 Non-return valve (field supply)
FHL1...3 Floor heating loop (field supply)
Field wiring configuration A
Field wiring configuration B
Details on pump configuration can be found under
"8.3. Pump operation configuration" on page 24.
NOTICE
When closing several loops in the system by remotely
controlled valves, it might be required to install a by-pass
valve (9) to avoid the flow switch safety device from being
activated. See also "Application 2" on page 4.
NOTICE
Wiring of the 2-way valve (13) is different for a NC (normal
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.
CAUTION
Be sure that the boiler and the integration of the boiler
in the system is in accordance with relevant European
and national regulations.
Daikin can not be put responsible for incorrect or
unsafe situations in the boiler system.
Boiler
thermostat input
Boiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional)
K1A Auxiliary relay for activation of EKHV* unit
(field supply)
K2A Auxiliary relay for activation of boiler (field supply)
Boiler
thermostat input
Boiler thermostat input
C Cooling demand room thermostat (optional)
H Heating demand room thermostat (optional)
Com Common room thermostat (optional)
K1A Auxiliary relay for activation of bolier unit
(field supply)
KCR Permission signal for the auxiliary boiler
M
FHL1
FHL2
FHL3
6
7
4321 9 18
16 17
15
8
17
11
12
5
123 4
K1A
K1A
K2A
X
Y
K2A
Boiler
thermostat input
L
N
EKHV*/auto
/ Boiler
A
EKHV*
X2M
H
Com
X1 X2
X
Y
K1A
KCR
EKRP1HB*
Boiler
thermostat input
12
3 4
HC
Com
K1A
EKHV*
X2M
EKRTR*
12
3 4
C
Com
H
K1A
EKHV*
X2M
EKRTW*