Installation manual
36
EKHVH/X016BB6V3 + EKHVH/X016BB6+9WN
Daikin Altherma indoor unit
4PW64331-1 – 07.2010
6 DT for heat pump domestic water heating mode
00 Start 2 2~20 1 °C
01 Stop 2 0~10 1 °C
02 Not applicable. Do not change the default value. — — — —
Domestic water heating storage and reheat timing operation setup
03 Scheduled time storage 1 (ON) 0/1 1 —
04 Scheduled time storage start time 1:00 0:00~23:00 1:00 hour
05 Scheduled time reheat or continuous reheat 0 (OFF) 0/1/2 1 —
06 Scheduled time reheat start time 15:00 0:00~23:00 1:00 hour
07 Domestic hot water reheat set point 45 30~50 1 °C
08 Domestic hot water reheat set point hysteresis 10 2~20 1 °C
7 Dual set point control
00 Not applicable. Do not change the default value. — — — —
01 Not applicable. Do not change the default value. — — — —
02 Dual set point control status 0 (OFF) 0/1 — —
03 Second set point heating
10
1~24 /
25~55
1°C
04 Second set point cooling 7 5~22 1 °C
8 Domestic water heating mode timer
00 Minimum running time 5 0~20 1 min
01 Maximum running time 30 5~95 5 min
02 Anti-recycling time 0.5 0~10 0.5 hour
03 Not applicable. Do not change the default value. — — — —
04 Additional running time at [4-02]/[F-01] 95 0~95 5 min
9 Heating and cooling set point ranges
00 Heating set point upper limit 55 37~55 1 °C
01 Heating set point lower limit 25 15~37 1 °C
02 Cooling set point upper limit 22 18~22 1 °C
03 Cooling set point lower limit 5 5~18 1 °C
04 Overshoot setting
(b)
1 1~4 1 °C
Automatic set back function
05 Set back function 0 (OFF) 0/1 1 —
06 Set back operation start time 23:00 0:00~23:00 1:00 hour
07 Set back operation stop time 5:00 0:00~23:00 1:00 hour
08 Leaving water set back value 2 0~10 1 °C
A Quiet mode type
00 Quiet mode type 0 0/2 — —
01 Satus 3———
02 Not applicable. Do not change the default value. 1
(c)
Read only — —
03 Not applicable. Do not change the default value. 0
(c)
Read only — —
04 Not applicable. Do not change the default value. 0
(c)
Read only — —
b Not applicable
00 Not applicable. Do not change the default value. 0
(c)
Read only — —
01 Not applicable. Do not change the default value. 0
(c)
Read only — —
02 Not applicable. Do not change the default value. 0
(c)
Read only — —
03 Not applicable. Do not change the default value. 0
(c)
Read only — —
04 Not applicable. Do not change the default value. 0
(c)
Read only — —
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value