Si38-606 Other Control
Function 61
5.2 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adapter is required.
[Demand 1 setting]
[Demand 2 setting]
Other protection control functions have precedence over the above operation.
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%
Setting Standard for upper limit of power consumption
Demand 2 setting 2 (factory setting) Approx. 40%