Daikin FXHQ-M Bedienungsanleitung Seite 18

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 20
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 17
Indoor Unit • Large concealed ceiling unit • FXMQ-MA
•VRV
®
Systems • Indoor Unit
16
12 Installation
12 - 1 Suspension Bolt Pitch Position
AM052,002QMXF
3P086156-2-5
Suspension bolt (x4)
Indoor unit
1,148
1,100
1,296
1,380
Inspection hatch 600
Approx. 150 mm
Air outlet
1,100 or more
(service space)
Air inlet
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Indoor unit
NOTES
1 Install a canvas duct to the air discharge outlet and air inlet so that vibration from the machine body is not transmitted to the duct or ceiling. You should also apply acoustic (insulation material) to the inside of the duct, and
vibration insulation rubber to the suspension bolts.
2 Install suspension bolts.
Use bolts of 10 mm diameter.
Install the equipment where supporting structures are strong enough to bear the equipment’s weight. Use embedded inserts or anchor bolts with new buildings and hole-in-anchors with old buildings.
NOTE
1 All the above parts are to be procured in the field.
Seitenansicht 17
1 2 ... 13 14 15 16 17 18 19 20

Kommentare zu diesen Handbüchern

Keine Kommentare