EDUS39-600-F1_a Installation
FXFQ-M 27
Ceiling work
(2) Adjust the unit to the correct position for installation.
(Refer to Section 4. (1) PREPARATIONS BEFORE
INSTALLATION, P. 67.
(3) Make sure the unit is horizontally level.
The indoor unit is equipped with a built-in drain
pump and float switch. At each of the unit’s 4 cor-
ners, verify that it is level by using a waterlevel or a
water-filled vinyl tube.
If the unit is inclined against condensate flow, the
float switch may malfunction and cause water to
drip.
(4) Remove the washer-fixing plate (7) used for preventing
the washer from falling and tighten the upper nut.
(5) Remove the paper pattern for installation (5).
6-2 For existing ceilings
(6) Adjust the height and position of the unit.
Refer toPREPARATIONS BEFORE INSTALLATION-(1).
(7) Perform steps (4), (5) in “6-1 For new ceilings”.
7. REFRIGERANT PIPING WORK
7-1 GENERAL INSTRUCTIONS
For refrigerant piping of outdoor units, see the installation man-
ual attached to the outdoor unit.
Before refrigerant piping work, check which type of refriger-
ant is used. Proper operation is not possible if the types of
refrigerant are not the same.
The outdoor unit is charged with refrigerant.
DANGER
Refrigerant gas may produce toxic gas if it comes in contact
with fire such as from a fan, heater, stove or cooking device.
Exposure to this gas could result in severe injury or death.
NOTE
Use a pipe cutter and flare suitable for the type of refriger-
ant.
To prevent dust, moisture or other foreign matter from infiltrat-
ing the tube, either pinch the end or cover it with tape.
Do not allow anything other than the designated refrigerant to
get mixed into the refrigerant circuit, such as air. If any refrig-
erant gas leaks while working on the unit, ventilate the
room immediately. .
7-2 Connecting the refrigerant piping
When connecting the flare nut, coat the flare both inside
and outside with ester
oil or ether oil and initially tighten by
hand 3 or 4 turns before tightening firmly.
To prevent flare nut cracking and gas leaks, be sure to use
both a spanner and torque wrench together, as shown in the
drawing below, when connecting or disconnecting pipes to/
from the unit.
Paper pattern for
installation 5)
Center of the unit
Center of ceiling opening
Ceiling material
Lower surface
of ceiling
[Height adjustment of the unit.]
Screws 6)
(attached)
[Installation of paper pattern for installation]
Water level
Vinyl tube
Ester oil or ether oil.
Torque wrench
Spanner
Piping union
Flare nut