Page 6 of 36 / OM 1169-1
Remote Controller Installation
Figure 8: Through the wall hole location details
Align the center of the wall
hole with the center of the
access hole on the controller
lower case when planning the
installation.
5/16 to 3/8
External view of the remote controller
Access hole
5/16 to 3/8
Lower case
Through hole
1-15/16
1-9/16
Wiring The Remote Controller
Note: Switchboxandcontrolwiringarenotincluded.DonottouchtheremotecontrollerPC-board.
Wiring Specications:
Wiring Type: ....................... Non-shielded, 2-conductor, stranded copper cable.
Wiring Size: ........................ AWG 18 or 16
Wiring Length: ................... Maximum 330 feet (100m)
Note: See also the “Wiring Diagram Label” located inside the unit’s control box cover.
Figure 9: Remote controller wiring details
Cable attachment guideline
Lower case
Upper case
PC-board
Clamp
Cable attachment
point
Cross-section-
Secure the cable at
the attachment point
by using furnished
clamping material.
Clamp
Connects to P1 & P2 at the unit
low voltage terminal block X2M
Low voltage wire entry
Low Voltage
Terminal Block (X2M)
Unit Control Box
9101112T1 T2F1 F2 F1 F2 P2P1
REMOTE
CNTRL
TO OUT/D
BRNRED ORG YLW BLK BLUWHT PNKGRY PPL YLWSKY BLU
UNIT
TRANSMISSION
WIRING
FORCED
PUMP
INTERLOCK
PUMP
REQUESTOFF