Page 18 of 36 / OM 1169-1
Setup Guide
Setting The Setback On/Off Differential
Note: SetbackCongurationwon’tbeavailableifyouhave
notenabledthesetbackcontrol(Fieldsetting1e-2-04
is necessary).
Determine the point when unit is turned off again from
the setback control (the unit is turned on by setback con-
trol when room temperature is above the setup setpoint
or below the setback setpoint)
Step 1.
Press and hold the “Cancel” button for 4 seconds or longer, to
enter “Service Settings” menu screen.
Press and hold the “Cancel”
button for 4 seconds.
Step 2.
Press the ▼ button to select
Energy Saving Options
. Press
the Menu/OK button.
Setting
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
1/3
Step 3.
Press the ▼ button to select
Setback Conguration
. Press
the Menu/OK button.
Setting
Energy Saving Options
Setpoint Range Limitation
Setback Configuration
Step 4.
Select the temperature item with ◄► buttons. Change the
temperature with ▼▲ buttons.
Setup setpoint - 4°F as default (2 - 10°F selectable)
Setback setpoint + 4°F as default (2 - 10°F selectable)
Setting
Setpoint Configuration
Recovery Differential
Cool Heat
4
F
+ 4
F
Setting The Minimum Differential Between
Cooling and Heating Setpoints
Step 1.
Press and hold the “Cancel” button for 4 seconds or longer, to
enter “Service Settings” menu screen.
Press and hold the “Cancel”
button for 4 seconds.
Step 2.
Press the ▼ button to select
Min Setpoints Differential
.
Press the Menu/OK button.
Setting
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
1/3
Step 3.
Select the “Min Setpoints Differential” item with ▼▲ but-
tons.
Note: Defaultis2°F,congurable0–7°F(0–4°C)
Setup setpoint - 4°F as default (2 - 10°F selectable)
Setback setpoint + 4°F as default (2 - 10°F selectable)
When Multi zone controller is connected, the differential is
set to 0°F automatically and is not adjustable.
Step 4.
Change the differential value with ▼▲ buttons. Press the
Menu OK button.
Setting
Min Setpoint Differential
Min Setpoints Differential
2
F
Press Menu/OK button.