INDOOR UNIT FDYQN200PV1 FDYQN250KV1
OUTDOOR UNIT RQ200KY1 RQ250KY1
Rated Capacity
Cool (kW) 20.0 24.0
Heat (kW) 22.4 26.8
Power Input (Rated)
Cool (kW) 6.47 8.14
Heat (kW) 6.22 7.95
E.E.R./C.O.P. C/H 3.09-3.60 2.95/3.37
Air Flow Rate (Rated) l/s 1200 1400
Indoor Sound Level (@1.5m) dBA 51 51
ESP Settings STD/HI STD/HI
Indoor Fan Speeds HI/LO HI/LO
Dimensions
(H x W x D)
Indoor (mm) 500x1410x910 500 x 1410 x 910
Outdoor (mm) 1680 x 930 x 765 1680 x 1240 x 765
Weight
Indoor (kg) 87 98
Outdoor (kg) 205 285
Power Supply Ø V/HZ 3 phase, 415V, 50Hz
Compressor Type Scroll
Refrigerant R410A
Refrigerant Control Electronic
Refrigerant Pipe Size
Liq (mm) Ø 9.5 (Brazed)
Gas (mm) Ø 22.2 (Brazed) Ø 22.2 (Brazed)
Drain Pipe Size BSP 3/4 inch internal thread
Supply Air Conn. mm 827 x 376 (Flange) 939 x 376 (Flange)
Return Air Conn. mm 1118x350 (Flange) 1118 x 350 (Flange)
Max Actual Pipe Length m 50
Max Level Difference m 30
Pre Charged Length m 0 0
Operating Range
Cool (°CDB) -5 to 43
Heat (°CWB) -20 to 15.5
Outdoor Sound Level
@ 1 Metre from front of unit
Pressure dBA (C/H) 57 60
NOTES
• Ratedcapacityismeasured
in accordance with
AS/NZS 3823.1.2.
• Thecooling(orheating)
capacities will be reduced
below the rated values as
the outside temperature
approaches the maximum (or
minimum) temperature limits.
• Outdoorsoundpressurelevels
are determined in accordance
with JIS8615.
• Outdoorsoundlevelsare
determined in an anechoic
chamber and may differ once
the unit is installed due to
ambient conditions.
• Outdoorsoundpowerlevelsare
determined in accordance with
EPA regulations.
• TheDaikin5yearwarranty
applies only to products in
this brochure purchased and
installed in Australia or New
Zealand. It does not apply to
any non Daikin components
used in the installation (e.g.
ducting, air outlets, zone
motors etc.).
• Duetoongoingproduct
development, specifications
are subject to change
without notice.
FDYQN200/250KV1 RQ200KY1 RQ250KY1
INDOOR UNIT OUTDOOR UNIT
• Highstrengthgalvanizedsteelcasing.
• Designofindoorunitsallowsforinstallationintolimited
roof space.
• Canbedismantledforeasierinstallationinlimited
roof space.
• Microprocessor-controlledoperationandmonitoring.
FEATURES OF HYBRID OUTDOOR UNITS
• NightQuietModereducessoundlevelsevenfurther.
• Re-designedReluctanceDCScrollCompressoroffers
superior energy savings performance.
• Intelligentdefrostforhighheatoutputatlowwinter
outdoor temperatures.
• Certiedoperationdownto-20inheating
and up to 43 in cooling.
• PEcoatedheatexchangersforgreaterprotection
against corrosion.
• Upto50mofrefrigerantpipingallowsexibility
of location.
• DCFanMotor–PowerfulNeodymiummagnetsenables
superior efficiencies to conventional types.
Kommentare zu diesen Handbüchern