Daikin RX20J3V1B Installationshandbuch

Stöbern Sie online oder laden Sie Installationshandbuch nach Wärmepumpen Daikin RX20J3V1B herunter. Daikin RX20J3V1B Installation manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Accessories
Precautions for Selecting the Location
3P141697-6D (M04B140A)
DAIKIN AIR CONDITIONER
Construct a large canopy.
Construct a pedestal.
Install the unit high enough off the
ground to prevent burying in snow.
Accessories supplied with the outdoor unit:
(A) Installation Manual
(B) Drain plug
There is on the bottom
packing case.
Cannot be installed hanging from ceiling or stacked.
1
1
OUTDOOR UNIT
1)
Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the
neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 9.5 feet away from television and radio sets. This is to
prevent interference to images and sounds. (Noises may be heard even if they are more than 9.5 feet away
depending on radio wave conditions.)
8)
In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9)
Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
Note
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
2) Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a
baffle plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the
snow will not affect the unit.
CAUTIONS
Indoor/Outdoor Unit Installation Drawings
Installation
Outdoor Unit Installation Guidelines
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe’s cut line.
Wrap the insulation
pipe with the finishing
tape from bottom to top.
Caulk
pipe hole
gap
with putty.
(F
oot bolt-hole ce
ntres)
22 13/16 in
(Foot bolt-hole
centres)
13 in
9.8 in from wall
Allow space for piping
and electrical servicing.
Allow 11.8 in of
work space below
the ceiling surface.
If there is the danger of the unit falling
or overturning, fix the unit with
foundation bolts, or with wire or other
means.
If the location does not have good
drainage, place the unit on a level
mounting base (or a plastic pedestal).
Install the outdoor unit in a level
position. Failure to do so may result in
water leakage or accumulation.
Level mounting base
(available separately)
Clamping material
Insulation tube
Service lid
Tape
Also insulate the connection on the outdoor unit.
Use tape or insulating material on all connections to
prevent air from getting in between the copper piping
and the insulation tube.
Be sure to do this if the outdoor unit is installed above.
More than 3 15/16 More than 13 3/4
Side view
47 3/16
or less
More than 1 15/16 More than 1 15/16
Top view
More
than 3 15/16
More than 13 3/4
Top view
More than 3 15/16
More than 13 3/4
More than 1 15/16
For installation of the indoor units, refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)
Install the unit horizontally.
The unit may be installed directly on a concrete verandah or a solid place if drainage is good.
If the vibration may possibly be transmitted to the building, use a vibration-proof rubber (field supply).
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines
below.
For any of the below installation patterns, the wall height on the exhaust side should be 4 ft or less.
Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without
connecting the indoor unit in order to add another indoor unit later.
Make sure no dirt or moisture gets into either side of the embedded branch piping.
See “6 Refrigerant Piping Work” in “Outdoor Unit” for details.
It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
CAUTION
Wall facing one side
Walls facing two sides
Walls facing three sides
Unit: in.
Selecting a Location for Installation of the Indoor Units
Outdoor Unit
Outdoor Unit
Level
difference: 25 ft
max.
(Heat pump
unit only)
Level
difference:
49 ft max.
Indoor Unit
Outdoor Unit
Drain-water hole
Bottom frame
Drain plug
While pressing
Hose (available commercially,
inner dia. 5/8 in)
Coat here with refrigeration machine oil
Torque wrench
Piping union
Flare nut
Spanner
Flare nut tightening torque
Flare nut for φ1/4 10.5-12.7 ft-lbf
Flare nut for φ3/8 24.1-29.4 ft-lbf
Flare nut for φ1/2 36.5-44.5 ft-lbf
Flare nut for φ5/8 45.6-55.6 ft-lbf
Liquid pipe
19.5-23.8 ft-lbf
Gas pipe
35.5-44.0 ft-lbf
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Be sure to
place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring
(Cut exactly at
right angles.)
Remove burrs
Check
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
Level
difference:
49 ft max.
Indoor Unit
Outdoor Unit
Level
difference:
25 ft max.
(Heat pump
unit only)
The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the
outdoor and indoor units, are listed below. (The shorter the refrigerant piping, the better the performance. Connect so
that the piping is as short as possible. Shortest allowable length per room is 9.8 ft.)
1 Installing Outdoor Unit
When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Indoor/Outdoor Unit
Installation Drawings.”
If drain work is necessary, follow the procedures below.
2. To prevent gas leakage, apply refrigeration machine oil on both inner and outer surfaces of the flare.
(Use refrigeration oil for R410A)
3 Refrigerant Piping
1.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas.
7 Flaring the Pipe End
1. Cut the pipe end with a pipe cutter.
2. Remove burrs with the cut surface facing
downward so that the chips do not enter the pipe.
3. Put the flare nut on the pipe.
4. Flare the pipe.
5. Check that the flaring is properly made.
2 Drain Work
Use drain plug for drainage.
If the drain port is covered by a mounting base or floor surface, place
additional foot bases of at least 1 3/16” in height under the outdoor unit’s feet.
In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain
water may freeze, impairing heating performance.)
If the outdoor unit is positioned higher than the indoor
units.
If the outdoor unit is positioned otherwise.
(If lower than one or more indoor units)
Outdoor unit capacity class
Piping to each indoor unit
Total length of piping between all units
2MXS18
82 ft max.
148 ft max.
Outdoor unit capacity class
Total length of piping for all rooms
2MXS18
98 ft
Pipe size
O.D.: 1/4” / Thickness: 0.031”
O.D.: 3/8”, 1/2” / Thickness: 0.031”
O.D.: 5/8” / Thickness: 0.039”
Pipe insulation
I.D.: 0.315-0.393” / Thickness: 0.393” min.
I.D.: 0.472-0.590” / Thickness: 0.511” min.
I.D.: 0.630-0.787” / Thickness: 0.511” min.
5 Charging with Refrigerant
If the total length of piping for all rooms exceeds the figure listed below, additionally charge with 0.22 oz/ft of
refrigerant (R410A) for each additional feet of piping.
6 Refrigerant Piping Work
Cautions on pipe handling
Protect the open end of the pipe against dust and moisture.
All pipe bends should be as gentle as possible. Use a pipe bender for
bending.
(Bending radius should be 1 3/16” to 1 9/16” or larger.)
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052kW/mK (0.024 to 0.030 Btu/fth°F)
Refrigerant gas pipe’s surface temperature reaches 230°F max.
Choose heat insulation materials that will withstand this temperature.
Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.
Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Even though the shut-off valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed
for a long period of time.
CAUTION
4 Purging Air and Checking Gas Leakage
When piping work is completed, it is necessary to purge the air and check for gas leakage.
Refer to “Purging Air and Checking Gas Leakage”.
Purging Air and Checking Gas Leakage
If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.
Use a hexagonal wrench (3/16”) to operate the shut-off valve rod.
All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.
(1) Connect projection side (on which worm pin is pressed) of charging hose (which comes from gauge manifold) to
gas shut-off valve’s service port.
(2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)
(3) Apply vacuum pumping. Check that the compound pressure gauge reads –29.9 in Hg. Evacuation for
at least 1 hour is recommended.
(4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.
(Leave as is for 4-5 minutes and make sure the coupling meter needle does not go back.
If it does go back, this may indicate the presence of moisture or leaking from connecting parts. After inspecting all
the connection and loosening then retightening the nuts, repeat steps 2 – 4.)
(5) Remove covers from liquid shut-off value and gas shut-off valve.
(6) Turn the liquid shut-off valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.
After the check is complete, wipe all soapy water off.
(7) Disconnect charging hose from gas shut-off valve’s service port, then fully open liquid and gas shut-off valves.
(Do not attempt to turn valve rod beyond its stop.)
(8) Tighten valve lids and service port caps for the liquid and gas shut-off valves with a torque wrench at the specified
torques. See “3 Refrigerant Piping” in “Outdoor Unit” for details.
FOR USE WITH “CTXS09DVJU” INDOOR UNIT ONLY
Precautions on Installation
Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts. (Prepare four sets of
M3/8” or M7/16” foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 3/4” from the foundation surface.
3/4”
Valve cap tightening
torque
Service port cap
tightening torque
7.9-10.8 ft-lbf
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the unit life.
3)
Never use piping which has been used for previous installations. Only use parts which are provided with the unit.
4) Do never install a refrigerant drier to this unit.
5) The drying material may dissolve and damage the system.
6) Incomplete or improper flaring may cause refrigerant gas leakage.
Set exactly at the position shown below.
A
Flaring
Die
A 0 ~ 0.020”
Clutch-type
Flare tool for R410A
0.039 ~ 0.059”
Clutch-type (Rigid-type)
0.059 ~ 0.079”
Wing-nut type (Imperial-type)
Conventional flare tool
Pump Down Operation
Forced Operation
Gas shut-off valve
Close
Hexagonal
wrench
Liquid shut-off
valve
Valve lid
Service PC-board
Operation Mode
switch (SW2)
Forced Operation
switch (SW1)
(1) Remove the valve lid from liquid shut-off valve and gas
shut-off valve.
(2) Carry out forced cooling operation.
(3) After five to ten minutes, close the liquid shut-off valve
with a hexagonal wrench.
(4) After two to three minutes, close the gas shut-off valve
and stop forced cooling operation.
(1) Turn the Operation Mode switch (SW2) to “COOL.”
(2) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to
stop forced cooling.
In order to protect the environment, be sure to pump
down when relocating or disposing of the unit.
Warning
When the piping work is completed, it is necessary to purge the air and check for gas leakage.
1) Do not place any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When a refrigerant gas leak occurs, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the
environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.
Warning
Safety Precautions
WARNING
• After completing installation, test the unit to check for installation errors. Give the user adequate
instructions concerning the use and cleaning of the unit according to the Operation Manual.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to lose, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the unit's weight.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
Electrical work should be carried out in accordance with the installation manual and the national, state and local electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. Follow all appropriate electrical codes.
Use the specified types of wires for electrical connections between the indoor and outdoor units. Follow all state and local electrical codes.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating, fire or euipment damage.
• After all installation is complete, check to make sure that no refrigerant is leaking.
(The refrigerant produces a toxic gas if exposed to flames.)
• The following safety symbols are used throughout this manual:
Be sure to observe this instruction.
Be sure to establish a proper
earth grounding connection.
Never attempt.
After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock,fire or equipment damage.
When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting in injury.)
• If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
• Be sure to establish a ground. Do not ground the unit to a utility pipe, arrester, or telephone ground.
Incomplete or inadequate grounding may cause equipment damage, or electrical shock and personal injury. A high surge
current from lightning or other sources may cause damage to the air conditioner.
• Install an leak circuit breaker, as required. If an leak circuit breaker is not installed, electric shock may result.
Be sure to install a ground fault circuit interrupter breaker. Failure to install a ground fault circuit interrupter breaker may result in electrically shocks or personal injury.
During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the shut-off valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the shut-off valve is open during pump-down, air will be sucked in when the compressor is run, causing
abnormally high pressure whichcould lead to equipment damage and personal injury.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible.
Do not use an extension cord. Do not put other loads on the power supply. Use a only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock,fire or equipment damage.)
WARNING
CAUTION
Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
Failure to follow any of CAUTION may in some cases result in grave consequences.
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into WARNINGS and CAUTIONS. Be sure to follow all the
precautions below: they are all important for ensuring safety.
Safety Precautions
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual. Inadequate piping may cause water damage.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
• Note
for installing the outdoor unit. (For heat pump model only.) In regions of the country where the outside temperature is at or
below the freezing point, the drain may freeze. If so, it is recommended that an electric heater be installed in order to protect the drain from freezing.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - DAIKIN AIR CONDITIONER

AccessoriesPrecautions for Selecting the Location3P141697-6D (M04B140A)DAIKIN AIR CONDITIONERConstruct a large canopy.Construct a pedestal.Install the

Seite 2 - Wiring error check

WiringRoomARoom ATo room BRoomBOutdoor unitIndoor unitSafety breakerEarth leakagecircuit breaker60Hz 208/230VBe sure to use the dedicated circuits.If

Kommentare zu diesen Handbüchern

Keine Kommentare