Pipe size selection
For an outdoor unit multi installation (REYQ18~48P +
REYHQ16~24), select the pipe size in accordance with the
following figure.
A. Piping between outdoor unit and refrigerant branch kit
B. Piping between outdoor unit multi connection piping units
Choose from the following table in accordance with the outdoor unit total capacity type, connected
downstream.
E. Piping between refrigerant branch kit and BS unit
Pipe size for direct connection to indoor unit must be the same as the connection size of indoor unit.
Choose from the following table in accordance with the indoor unit total capacity type, connected
downstream.
Outdoor unit
capacity type (Hp)
Piping outer diameter size (mm)
Indoor unit
capacity type
Piping outer diameter size (mm)
Suction gas pipe HP/LP gas pipe Liquid pipe Suction gas pipe HP/LP gas pipe Liquid pipe
8 19.1 15.9 9.5 <150 15.9 12.7 9.5
10 22.2 19.1 9.5 150≤x<200 19.1 15.9 9.5
12 28.6 19.1 12.7 200≤x<290 22.2 19.1 9.5
14+16 28.6 22.2 12.7 290≤x<420 28.6 19.1 12.7
18 28.6 22.2 15.9 420≤x<640 28.6 28.6 15.9
20+22 28.6 28.6 15.9 640≤x<920 34.9 28.6 19.1
24 34.9 28.6 15.9 ≥920 41.3 28.6 19.1
26~34 34.9 28.6 19.1
36 41.3 28.6 19.1 F. Piping between refrigerant branch kit or BS unit and indoor unit
Choose from the following table in accordance with the capacity type of the connected indoor unit.
38~48 41.3 34.9 19.1
Indoor unit
capacity type
Piping outer diameter size (mm)
C. Piping between outdoor unit multi connection piping kit and outdoor unit
Choose from the following table in accordance with the capacity type of the connected outdoor unit.
Suction gas pipe Liquid pipe
20, 25, 32, 40, 50 12.7 6.4
Outdoor unit
capacity type (Hp)
Piping outer diameter size (mm) 63, 80, 100, 125 15.9 9.5
Suction gas pipe HP/LP gas pipe Liquid pipe 200 19.1 9.5
8+10 22.2 19.1 9.5 250 22.2 9.5
12 28.6 19.1 12.7
14+16 28.6 22.2 12.7 D. Equalizer piping (outdoor units only)
Piping outer diameter size (mm) 19.1
How to calculate the additional refrigerant to be charged
Additional refrigerant to be charged R (kg)
R should be rounded off in units of 0.1 kg
Example for refrigerant branch using refnet joint and refnet header for
REYQ34. REYQ34 = REMQ8+REMQ10+REMQ16, the indoor unit
connection ratio = 120% and the piping lengths are as below.
C
A
BE
F
C C
DD
F
The refrigerant charge of the system must be less than
100 kg. This means that in case the calculated
refrigerant charge is equal to or more than 95 kg you
must divide your multiple outdoor system into smaller
independent systems, each containing less than 95 kg
refrigerant charge.
For factory charge, refer to the unit name plate.
R =
REYQ
18+20 Hp
22+24 Hp
26 Hp
28+30 Hp
32~40 Hp
42 Hp
44+46 Hp
48 Hp
16~32 Hp
34~48 Hp
>100%
≤130%
0.5 kg
>100%
≤120%
0.5 kg
>120%
≤130%
1.0 kg
[(X1 x Ø22.2) x0.37] + [(X2 x Ø19.1) x0.26] +
[(X
3 x Ø15.9) x0.18] + [(X4 x Ø12.7) x0.12] +
[(X
5 x Ø9.5) x0.059] + [(X6 x Ø6.4) x0.022]
+ A + Bx 1.02
REY(H)Q
1.0 kg
1.5 kg
2.0 kg
2.5 kg
3.0 kg
3.5 kg
4.0 kg
4.5 kg
REYHQ
16 Hp
20 Hp
22+24 Hp
1.0 kg
1.5 kg
2.0 kg
X1...6 = Total length (m) of liquid piping size at Øa
A = Weight according to table A
B = Weight according to table B in function of indoor unit connection ratio
R = [ [50x0.26]+[1x0.18]+[3x0.12]+[156x0.059]+[20x0.022] ]x1.02+3.0+0.5
a : Ø19.1x30 m
b : Ø19.1x20 m
c : Ø9.5x10 m
f : Ø9.5x10 m
g : Ø9.5x10 m
h : Ø9.5x10 m
k : Ø9.5x20 m
l : Ø9.5x20 m
p : Ø6.4x10 m
r : 12.7x3 m
m: Ø9.5x20 m s : Ø9.5x3 m
u : Ø15.9x1 m
d : Ø9.5x10 m
e : Ø9.5x10 m
i : Ø9.5x10 m
j : Ø9.5x10 m
n : Ø9.5x10 m t : Ø9.5x3 m
o : Ø6.4x10 m
= 27.148 ⇒ R = 27.1 kg