English 3
FOR THE FOLLOWING ITEMS, TAKE SPECIAL
CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Also review the SAFETY PRECAUTIONS
b. Items to be checked at time of delivery
c. Points for explanation about operations
2-4 NOTE TO INSTALLER
Be sure to instruct customers how to properly operate the
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
Do not use in seaside locations with a lot of salt in the air, fac-
tories and other locations where the voltage fluctuates, in
automobiles, or in marine vessels.
3. SELECTING INSTALLATION SITE
When it may exceed 30°C and RH80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation (Thickness
10mm or more of glasswool or polyethylene form) is required.
(1) Select an installation site where the following conditions are
fulfilled and that meets with your customers approval.
Where is resistible against weight of the unit.
In the upper space (including the back of the ceiling) of the
unit where there is no possible dripping of water from the
refrigerant pipe, drain pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks the air passage.
Where condensate can be properly drained.
If supporting structural members are not strong enough
to take the units weight, the unit could fall out of place
and cause serious injury.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of combustible gas leakage.
Where sufficient clearance for maintenance and service
can be ensured. (Refer to Fig. 1)
Where the total piping length involving indoor unit and
outdoor unit is below the allowable piping length.
(See the installation mamual included with the outdoor
unit for 6. REFRIGERANT PIPING.)
Locations where a maintenance hole can be installed.
(Refer to Fig. 2)
CAUTION
Install the indoor and outdoor units, power supply wires and
transmission wires at least 1 meter away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient enough to eliminate the noise.)
(2) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling
before installing the unit.
Items to be checked
If not properly done, what is
likely to occur.
Check
Are the indoor and outdoor unit
fixed firmly?
The units may drop, vibrate or
make noise.
Is the gas leak test finished?
It may result in insufficient cool-
ing.
Is the unit fully insulated? Condensate water may drip.
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage
correspond to that shown on
the name plate?
The unit may malfunction or
the components burn out.
Are wiring and piping correct?
The unit may malfunction or
the components burn out.
Is the unit safely grounded? It may result in electric shocks.
Is wiring size according to
specifications?
The unit may malfunction or
the components burn out.
Is something blocking the air
outlet or inlet of either the
indoor or outdoor units?
It may result in insufficient cool-
ing.
Are refrigerant piping length
and additional refrigerant
charge noted down?
The refrigerant charge in the
system is not clear.
Items to be checked Check
Did you explain about operations while showing the instruction
manual to your customer?
Did you hand the instruction manual over to your customer?
The items with WARNING and CAUTION marks in the instruc-
tion manual are the items pertaining to possibilites for bodily injury
and material damage in addition to the general usage of
the product. Accordingly, it is necessary that you make a full expla-
nation about the described contents and also ask your customers to
read the instruction manual.
Outdoor-air
processing unit
(Upper face)
650 or more
530 or more
(Service space)
1100 or more
(Service space)
(length: mm)
Fig. 1