Daikin FXHQ-A Spezifikationen Seite 22

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 36
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 21
EDUS39-600-F5 Installation
FXHQ-M 21
(3-2) Remove the decoration panels (left and right) and the
protection net.
After removing the securing screws for the decoration
panels (one each), pull them forward in the direction of
the arrowand remove them. (Refer to Fig. 3)
Remove the securing screws for the protection net.
(Refer to Fig. 3)
Raise one side of the protection net upwardin the direc-
tion of the arrow (i) and remove back toward the arrow
(ii). (Refer to Fig. 4, 5)Take out the accessories.
(3-3) Remove the rear metal plate for transmission wire,
remote controller wire and refrigerant pipe.
It is necessary to drill the knock out hole in the remov-
able part. Knock down several times with a punch and
hammer and remove the removable part with pliers.
When setting the refrigerant pipe to the rear side,
remove the securing screws and the metal plate. (Refer
to Fig. 6)
(3-4) Remove the hanger brackets.
Loosen the 2 bolts (M8) used to attach the hanger
brackets which are on each side (4 places left and right)
to within 3/8 in.. (Refer to Fig. 7, 8)
After removing the securing screws (M5) for the hanger
brackets on the rear side, pull the hanger brackets back
in the direction of the arrow, and remove them. (Refer
to Fig. 8)
(4) Attach the suspension bolts. Use suspension bolts
which are W3/8 or M8-M10 in size.
Adjust the distance of the suspension bolts from the ceiling
in advance. (Refer to Fig. 9)
NOTE
Use a hole-in anchor for existing ceilings, and a sunken
insert, sunken anchor or other field supplied parts for new
ceilings to reinforce the ceiling to bear the weight of the
unit. Adjust clearance from the ceiling before proceeding
further.
Decoration panel
securing screw
(M4)
Decoration panel
Fig. 3
Protection net
securing screws (M4)
Decoration
panel
Decoration panel
securing screws (M4)
Decoration panel
Decoration
panel
Accessories
Fig. 4
Fig. 5
Protection net
(ii)
(i)
(ii)
(i)
Hook
Protection net
If it raises too much,
a hook stops catching
and falling out.
Removable part
(metal plate)
If setting the refrigerant pipe to
the rear side, remove this metal plate.
After removing, attach the resin bush
(Refer to Fig. 26)
Metal plate
securing
screw (M4)
Fig. 6
If setting the drain pipe to the
right side, block up the hole for
drain pipe with pate etc.
Indoor unit
Hanger bracket
3/8 or less
Length of loosening
should be less than 3/8
(Length : in.)
Fig. 7
Hanger bracket
fixing screw (M5)
Hanger bracket
Hanger bracket
setting bolt (M8)
Fig. 8
Ceiling slab
Anchor
Suspension bolt
False ceiling
1–2 3/16
(Length : in.)
All the above parts are field supplied.
Fig. 9
Seitenansicht 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 35 36

Kommentare zu diesen Handbüchern

Keine Kommentare