24 English
11. FIELD SETTING
Complete all the “1. Items to be checked after completion of work” on page 4.
Make sure that the installation and wiring work for the indoor and outdoor units is all completed.
Make sure that the following items are all closed: the control box lid of the indoor unit and the outer board
and piping cover of the outdoor unit.
<Field setting must be made from the remote controller and in accordance with installation conditions.>
Setting can be made by changing the “Mode No.”, “FIRST CODE NO.” and “SECOND CODE NO.”.
For setting procedures and instructions, see the manual provided with the remote controller.
NOTE
The “Mode No.” is normally set collectively for a group. In order to set each indoor unit individually and per-
form checks after the settings, specify the Mode No. in parenthesis.
Do not perform settings that are not listed in the table.
11-1 SETTING AIR FILTER SIGN
The filter sign that notifies you of the necessity for air filter cleaning is displayed on the LCD display
of the remote controller.
Change the SECOND CODE NO. below depending on the amount of dirt or dust in the room.
(As the factory setting, the FIRST CODE NO. 1 is set to the SECOND CODE NO. “01” for the long
time, and the FIRST CODE NO. 0 is set to the SECOND CODE NO. “01”, air filter contamination -
light.)
(Refer to Table 6)
Explain to the customer that filters need to be cleaned periodically to prevent clogging, and the time
that is set.
The periodical cleaning time for the filter can be shortened depending on the usage environment.
Table 6
are the settings when shipped from the factory.
11-2 AIRFLOW SETTINGS WHEN THERMOSTAT IS OFF
Set the flow rate according to the requirement of the environment after consultation with the customer.
(Refer to Table 7)
When the airflow is changed, explain the airflow rate setting to the customer.
Table 7
Setting Mode No.
FIRST
CODE NO.
SECOND CODE NO.
01 02 04
Cleaning time
10 (20)
1
For long
time
For short
time
Air Filter
contamination:
light/heavy
For long time
0
Approx.
2,500 hours
Approx.
1,250 hours
For short time
Approx.
200 hours
Approx.
100 hours
Setting Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Fan operation when thermostat
is OFF (Cooling/Heating)
Normal
11 (21) 2
01
Stop 02
Airflow rate when cooling
thermostat is OFF
LL airflow rate
12 (22) 6
01
Setting airflow rate 02
Airflow rate when heating
thermostat is OFF
LL airflow rate
12 (22) 3
01
Setting airflow rate 02
3P249378-4D_FM6.book Page 24 Thursday, December 15, 2011 10:00 AM