Troubleshooting SiBE04-624_B
100 Service Diagnosis
2.17 Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
Error Code
U4
Method of Error
Detection
The data sent from the outdoor unit is checked for problem.
Error Decision
Conditions
The data sent from the outdoor unit cannot be received without error, or the disable status of
signal transmission continues for 15 seconds.
Supposed
Causes
Wiring error
Breakage of relay wire (transmission wire)
Defective outdoor unit PCB
Defective fan motor
Defective indoor unit PCB
Troubleshooting
NO
Does the distance of
relay wire exceed
30 m?
(R18125)
YES
YES
Caution
Check the relay wire between the
indoor unit and the outdoor unit
for color and number.
Any improper wiring?
YES
Poor insulation
OK
Are the relay
wires and the earth
properly insulated?
Is the measured
value 30 to 50 V?
YES
NO
NO
Does LED A on the
outdoor unit blink?
Disconnect No. 3.
Measure the voltage between
No. 2 and 3 (Apply negative
terminal to No. 2 in DC range)
NO
(below 30 V or above 50 V)
Correct the relay wire
between the indoor unit and
the outdoor unit.
Replace the relay wire
between the indoor and the
outdoor unit.
Distance is to be within the
specified range (30 m or
less).
Replace the outdoor unit
PCB.
Replace the indoor unit
PCB (Control PCB).
Replace the outdoor unit
PCB.
YES
NO
Replace both the fan motor
and the outdoor unit PCB.
Rotate the
outdoor fan by hand.
Does the outdoor fan rotate
smoothly?
7 sec.
Voltage
Power on
15 sec. Stop
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check during
this period
Fault
determined