Troubleshooting by Remote Controller SiUS281117
Service Diagnosis 161
2.42 Refrigerant Shortage
Remote
Controller
Display
U0
Applicable
Models
RZR, RZQ
Method of Error
Detection
Refrigerant shortage is detected according to the electronic expansion valve opening degree
and measured temperatures and pressures.
Error Decision
Conditions
(In cooling operation)
When the electronic expansion valve opens fully and low pressure is below 14.5 psi
continuously for 30 minutes.
(In heating operation)
When the electronic expansion valve opens fully and the suction superheat is large (more than
68°F) continuously for 30 minutes.
Error code is displayed but the system operates continuously.
Supposed
Causes
The stop valve is not opened.
Insufficient refrigerant amount
Clogged refrigerant piping system
Troubleshooting
Note: Refrigerant shortage alarm is indicated but the operation continues.
Refer to P.181.
Open the stop valve.
Is the stop valve open?
Check the refrigerant
piping system for
clogging.
Collect refrigerant. After
vacuum drying is complete,
charge an appropriate
amount of refrigerant.
Is the refrigerant
amount appropriate?
NO
NO
YES
CHECK 8
YES
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution