Daikin EWAQ100DAYN Spezifikationen Seite 3

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 30
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 2
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1C
Operation manual
2
Electrical specifications
(1)
General EWAQ
240 260
Dimensions HxWxD
(mm)
2311x2000x4833
Weight
machine weight
(kg)
3150 3250
operation weight
(kg)
3189 3292
Connections
chilled water inlet and outlet
3" 3"
•evaporator drain
1/2"G 1/2"G
Internal water volume
(l)
39 42
Expansion vessel (only for
OPSP, OPTP and OPHP)
•volume
(l)
50 50
pre-pressure
(bar)
1.5 1.5
Safety valve
water circuit
(bar)
3.0 3.0
Pump (only for OPSP)
type
Ver tical in-line pump
model (standard)
TP 65-260/2 TP 65-260/2
Compressor
Type
semi-hermetic scroll
compressor
Qty x model
2x SJ240-4 +
2x SJ300-4
4x SJ300-4
Speed
(rpm)
2900 2900
Oil type FVC68D FVC68D
Oil charge volume
(l)
2x 6.2 +
2x 6.2
4x 6.2
Condenser
Nominal air flow
(m
3
/min)
1600 1600
No. of motors x output
(W)
8x 600 8x 600
Evaporator
Model
DV58 DV58
EWAQ
080 100 130 150
Power supply
YN
Phase
3~
•Frequency
(Hz)
50
•Voltage
(V)
400
•Voltage tolerance
(%)
±10
Unit
Nominal running current (A)
60 72 88 113
Maximum running current (A)
96 120 160 177
Recommended fuses
according to IEC 269-2
(A)
3x 125 gL 3x 160 gL 3x 200 gL 3x 200 gL
Compressor
Circuit 1
Circuit 2
(hp)
(hp)
15 + 15
20 + 20
13 + 13
13 + 13
15 + 15
15 + 15
Phase
3~
•Frequency
(Hz)
50
•Voltage
(V)
400
Nominal running current
Circuit 1
Circuit 2
(A)
(A)
39 + 39
51 + 51
35 + 35
35 + 35
39 + 39
39 + 39
Control and fan motor
Phase
1~
•Frequency
(Hz)
50
•Voltage
(V)
230 V
Maximum running current (A)
4x 1.5 4x 1.5 4x 1.6 4x 2.3
Pump
•Power
(kW)
2.2 2.2 3 3
Nominal running current (A)
4.5 4.5 6.3 6.3
Heater tape
(OP10)
Supply voltage
(V)
230 V ±10%
•Power (standard)
(OPSP)
(OPBT)
1x 300 W
2x 300 W
2x 300 W + 150 W
Optional field heater
maximum 1 kW
Recommended fuses
(A)
2x 10
EWAQ
180 210 240 260
Power supply
YN
Phase
3~
•Frequency
(Hz)
50
•Voltage
(V)
400
•Voltage tolerance
(%)
±10
Unit
Nominal running current (A)
131 144 162 181
Maximum running current (A)
209 233 262 290
Recommended fuses
according to IEC 269-2
(A)
3x 250 gL 3x 250 gL 3x 300 gL 3x 355 gL
Compressor
Circuit 1
Circuit 2
(hp)
(hp)
20 + 15
20 + 15
20 + 20
20 + 20
25 + 20
25 + 20
25 + 25
25 + 25
Phase
3~
•Frequency
(Hz)
50
•Voltage
(V)
400
Nominal running current
Circuit 1
Circuit 2
(A)
(A)
51 + 39
51 + 39
51 + 51
51 + 51
65 + 51
65 + 51
65 + 65
65 + 65
Control and fan motor
Phase
1~
•Frequency
(Hz)
50
•Voltage
(V)
230 V
Maximum running current (A)
6x 2.3 6x 2.3 8x 1.6 8x 1.6
Pump
•Power
(kW)
4444
Nominal running current (A)
8.0 8.0 8.0 8.0
Heater tape
(OP10)
Supply voltage
(V)
230 V ±10%
•Power (standard)
(OPSP)
(OPBT)
1x 300 W
2x 300 W
2x 300 W + 150 W
Optional field heater
maximum 1 kW
Recommended fuses
(A)
2x 10
Seitenansicht 2
1 2 3 4 5 6 7 8 ... 29 30

Kommentare zu diesen Handbüchern

Keine Kommentare