5. TEST OPERATION
Perform test operation according to the instructions in the installation manual attached to the indoor unit.
After refrigerant piping, drain piping, and electric wiring, operate according to the table to protect the unit.
[PRECAUTIONS]
1.
Refer to malfunction diagnosis label attached to the unit if it does not operate.
2.
Refer to the installation manual attached to the outdoor unit for individual operation system types.
Order Operation
(1) Open gas side stop valve.
(2) Open liquid side stop valve.
(3) Electrify crank case heater for 6 hours. (Not necessary for cooling type units)
(4) Set to cooling with the remote controller and push button to start operation.
(5) Push
button twice and operate in TEST OPERATION mode for 3 minutes.
(6) Push
button and confirm its operation.
(7) Push
button and operate normally.
(8) Confirm its function according to the operation manual.