OH08-1 Remote Controller (Wireless Type)
Control Systems 45
2
(Example)
If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “10”, FIRST CODE NO. to
“0”, and SECOND CODE NO. to “02”.
NOTE
The SECOND CODE NO. is factory set to “01”. However, for the following cases it is set to “02”.
Air Flow Direction Range Setting
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are equal.
(For group control, refer to the installation manual attached to the indoor unit for group control.)
MODE
NO.
FIRST
CODE
NO.
DESCRIPTION OF SETTING
SECOND CODE NO. NOTE)
01 02 03
10
0
Filter Contamination-
Heavy/Light (Setting
for spacing time of dis-
play time to clean air
filter) (Setting for when
filter contamination is
heavy, and spacing
time of display time to
clean air filter is to be
halved)
Ultra-long-
life type
light
approx.
10,000
hours
heavy
approx.
5,000
hours
-
Long-life
type
approx.
2,500
hours
approx.
1,250
hours
Standard
type
approx.
200 hours
approx.
100 hours
1
Long-life filter type (Setting of filter
sign indication time)
(Change setting when Ultra-long-life
filter is installed)
Long-life filter
Ultra-long-life
filter (1)
-
3
Spacing time of display time to
clean air filter count
(Setting for when the filter sign is
not to be displayed)
Display Do not display -
11
(Sprit
system)
0
Setting the number of connected
simultaneous operation system
indoor units.
Pair Twin Triple
12
(VRV
system)
1
ON/OFF input from outside (Set to
enable starting/stopping from
remote.)
Forced OFF input ON/OFF -
2
Thermostat differential changeover
(Set when using remote controller
thermostat sensor.)
C 0.5˚C -
13
0
High ceiling setting (Setting for
when installed in a ceiling higher
than 2.7 m)
Normal High Ceiling 1
High
Ceiling 2
1
Selection of Air Flow Direction (Set-
ting for when a blocking pad kit has
been installed)
F T W
4 Air Flow Direction Range Setting Upper Normal -
C: 3PA59585-23Y-6
2.2 BRC7E61W / BRC7E65