Daikin BRC1E51A7 Installationshandbuch Seite 11

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 32
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 10
English 9
<Ceiling work>
(1-3) Adjust the unit to the right position for installation.
(Refer to “4. PREPARATIONS BEFORE INSTALLATION-
(1)”.)
At this time, using the positioning jig for installation (15)
allows to confirm the position from under surface of the
unit to under surface of the ceiling.
(1-4) Check the unit is horizontally level.
CAUTION
The indoor unit is equipped with a built-in drain pump and float
switch. Verify that it is level by using a level or a water-filled
vinyl tube.
(If the unit is tilted against condensate flow, the float switch may
malfunction and cause water to drip.)
(1-5) Remove the washer fixing plate (7) used for preventing the
washer from falling and tighten the upper nut.
(1-6) Remove the paper pattern for installation (5).
(2) For existing ceilings
(2-1) Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using nut and washer from
upper/lower sides of hanger bracket. If you use the washer fixing plate (7), it will prevent the falling of
the washer.
(2-2) Adjust the height and position of the unit.
(Refer to “4.PREPARATIONS BEFORE INSTALLATION-(1)”.)
(2-3) Perform steps (1-4), (1-5) in (1) For new ceilings.
Fit the shorter side
of the convex.
Underside of
the ceiling
Positioning jig for
installation (15)
(attached)
Underside
of the unit
main body
Fig. 11
Level
Vinyl tube
[Maintaining horizontality]
Fig. 12
Field supply
Washer (3) (attached)
[Securing the hanger bracket]
Hanger bracket
Tighten (double nuts)
Fig. 13
Insert
Washer fixing plate (7)
[Securing the washer]
(attached)
Fig.
14
Seitenansicht 10