SeriesSystem air conditionerINSTALLATION MANUALMODELSRQYQ8PY1BRQYQ10PY1BRQYQ12PY1BRQYQ14PY1BRQYQ16PY1BRQYQ18PY1BRQYQ20PY1BRQYQ22PY1BRQY
5 English• For anti-corrosion type use nuts with resin washers. If the paint on nut connections comes off, the anti-corrosion effect may decrease.6. R
English 64. Remove the knock hole on the bottom frame and route the piping under the bottom frame.5. Gas side shutoff valve6. Liquid side shutoff valv
7 English(3) If the piping length between the outdoor units exceeds 2 m, create a rise of 200 mm or more in the gas line under a length of 2 m from th
English 86-5 Example of connection(Example) With REFNET header, indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8(Example) With REFNET joints B, indoor unit
9 EnglishPipe Sizes SelectionPiping between Outdoor Unit ~ Refrigerant Branch Connection (Part A)Calculation Method of Re-charging Amount of Refrigera
English 107. FIELD WIRINGCAUTION• All field wiring and components must be installed by a licensed electrician and must comply with relevant local and
11 EnglishNote• Open the knock holes with a hammer or the like.• After knocking out the holes, we recommend you remove any burrs and paint them using
English 12• When pulling the ground wire out, wire it so that it comes through the cut out section of the cup washer. (See the figure below.) An impro
13 EnglishNoteIf moisture might enter the piping, follow belows.(I.e., if doing work during the rainy season, if the actual work takes long enough tha
English 14<Tightening torque>(Refer to figure 34)1. Service port2. Cap3. Hex holes4. Shaft (valve body)5. Seal section [To open]1.Remove the cap
00_CV_3P226891-13Q.fm Page 2 Thursday, December 2, 2010 1:08 PM
15 English11-2 Procedure of Adding Refrigerant charging and check operationWARNING ELECTRIC SHOCK WARNING• Make sure to close the EL. COMPO. BOX lid b
English 163.Open the valve C (See the figure 31. The valve A, B and the liquid and gas side shutout valve must be left closed), and charge the refrige
17 English11-2-1 Refrigerant Charging Operation Procedure[Check operation]ProceduresOperational Conditions(Each of mentioned below is a standard oper
English 18LED indications : light-out : light-on : blnkingC/H SELECTORMODEHWL:INDMASTERSLAVEL.N.O.PDEMANDH1P H2P H3P H4P H5P H6P H7PLED indicatio
19 English Remote controller indications at check operation (for BRC1C62)A.Before check operationAfter check operation*1 Regardless of previous setti
English 2012. ONSITE SETTINGSNoteIn the case of a multi system, all onsite settings should be made on the master unit. Settings made on sub units are
21 English2.Calculate the smallest room volume (m3 )Incase like the following, calculate the volume of (A), (B) as a sin-gle room or as the smallest r
3P226891-13Q EM10A040(1012) HT00_CV_3P226891-13Q.fm Page 6 Thursday, December 2, 2010 1:08 PM
[Q8 · 10 · 12 type][Q14 · 16 type]Top view1, 2, 31, 2, 31, 2, 344figure 1figure 4figure 3≥10≥10≥10≥20≥20≥50≥50≥50≥200≥400 ≥400≥50≥10≥300 ≥300≥500≥500≥
figure 21figure 25A1234A-arrow viewB1B-arrow viewfigure 16figure 171111518-118-218-362344CD(C-arrow view)(D-arrow view)112345347682figure 181210987311
123410 101314115678912figure 33figure 27figure 29 figure 30123456789101211[In case of Q8 · 10 · 12 type] [In case of Q14 · 16 type]1132341456789111012
1 EnglishRQYQ8PY1BRQYQ10PY1BRQYQ12PY1BRQYQ14PY1BRQYQ16PY1BRQYQ18PY1BRQYQ20PY1BRQYQ22PY1BRQYQ24PY1BRQYQ26PY1BRQYQ28PY1BRQYQ30PY1BRQYQ32PY1BRQYQ34PY1BRQ
English 2• Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios to prevent picture i
3 EnglishNote• Be sure to connect an R410A indoor unit. See the catalog for indoor unit models which can be connected.• At above is the total capacity
English 43. SELECTION OF LOCATIONSelect a location for installation that meets the following conditions. Get the customer’s permission.1.There is no d