Air Handling Unit Connection • Heat pump
5
Air Handling Unit Connection • ERQ-AV1
2 Specifications
3 Options
Notes RLA is based on following conditions: indoor temperature: 27°CDB/19°CWB, outdoor temperature:
35°CDB
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is
not below or above listed range limits
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the value of MCA
Instead of fuse, use circuit breaker. MFA is used to select circuit breaker and the ground fault circuit
interrupter (earth leakage circuit breaker).
MSC means the maximum current during start up of the compressor
EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents
produced by equipment connected to public low-voltage system with input current > 16A and <= 75A per
phase
SSC means short-circuit power
2-3 Electrical Specifications ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B
ERQ-AV1
Item ERQ100 ERQ125 ERQ140
1 Cool/heat selector KRC19-26A6
2 Fixing box KJB111A
3 Central drain plug KKPJ5F180
Note: all options are kits